NAiS FP Series User Manual page 274

Applicable plc
Hide thumbs Also See for FP Series:
Table of Contents

Advertisement

FPΣ
Relay No.
Name
R9040
Not used
R9041
COM. 1 port PLC link
flag
R9042
COM. 2 port commu-
nication mode flag
R9043 to
Not used
R9046
R9047
COM.2 port commu-
nication error flag
COM.2 port reception
R9048
done flag during gen-
eral purpose commu-
nicating
R9049
COM.2 port transmis-
sion done flag during
general
purpose communicat-
ing
R904A to
Not used
R904F
R9050
MEWNET - W0
PLC link transmission
error flag
R9051 to
Not used
R905F
Description
Turns on while PLC link function is used.
This goes on when the general - purpose communication function is used.
It goes off when MEWTOCOL is used.
This goes on if a transmission error occurs during data
communication.
This goes off when a request is made to send data, using the F159 (MTRN)
instruction.
Turns on when the end code is received during the general - purpose com-
munication.
This goes on when transmission has been completed when using general -
purpose communication.
It goes off when transmission is requested when using general - purpose
communication.
When using MEWNET-W0
- turns on when transmission error occurs at PLC link.
- turns on when there is an error in the PLC link area settings.
13.5 Table of Special Internal Relays
13 - 25