FPΣ
Tip
There are two operation modes in which jogging feed can be carried out with the
FPΣ, one in which no target value is specified, and one in which feed stops when
the target value is reached.
Normal jogging feed (mode in which no target value is specified)
Pulses are output in accordance with the condition set for the data table, as long as
the condition is on.
Data table
DT300
Control code *1
DT301
DT302
Frequency *2
DT303
Mode in which output stops when the target value is reached (supported in
Ver. 2.0 and subsequent versions)
With Ver. 2.0 and subsequent versions of the FPΣ (control unit C32T2), a mode
can be used in which a target value is specified for jogging operation, and pulses
are stopped when that target value is reached. As shown below, the control code is
used to select this mode, and the target value (an absolute value) is then specified
in the data table.
Data table
DT300
DT301 Control code *1
DT302
DT303 Frequency *2
DT304
DT305 Target value *3
Pulse output diagram
XB
: H1110
(JOG command)
: 300 Hz
Y0 (Pulse)
Pulse output diagram
XB
: H11110
(JOG command)
: 300 Hz
Y0 (Pulse)
: K1000
6.4 Pulse Output Function
ON
OFF
300Hz
0Hz
ON
OFF
300Hz
0Hz
Target value matching
Pulse stopping
6 - 31