Specifications
Name
Boolean
Basic function instructions
On-delay
TML
timer
TMR
TMX
TMY
Auxiliary
F137
timer
(STMR)
(16- bit)
Auxiliary
F183
timer
(DSTM)
(32- bit)
Counter
CT
UP/DOWN
F118 (UDC)
counter
Shift register SR
Left/right
F119
shift register
(LRSR)
Control instructions
Master
MC
control relay
Master
MCE
control relay
end
Jump
JP
Label
LBL
Note
When TM256 or higher or CT256 or higher is set, the number of
steps is the number in parentheses.
13 - 46
Symbol
Description
After set value "n" × 0.001 seconds, timer contact
"a" is set to on.
After set value "n" × 0.01 seconds, timer contact
TMa
n
"a" is set to on.
After set value "n" × 0.1 seconds, timer contact
"a" is set to on.
After set value "n" × 1 second, timer contact "a"
is set to on.
After set value "S" × 0.01 seconds, the specified
Y,R,L
output and R900D are set to on.
F137 STMR, S, D
After set value "S" × 0.01 seconds, the specified
Y,R,L
output and R900D are set to on.
F183 DSTM, S, D
Decrements from the preset value "n".
Count
CT
n
Reset
Increments or decrements from the preset value
UP/DOWN
F118 UDC
"S" based on up/down input.
Count
S
Reset
D
Shifts one bit of 16-bit [word internal relay (WR)]
Data
SR WR n
data to the left.
Shift
Reset
Shifts one bit of 16-bit data range specified by
L/R
F119 LRSR
"D1" and "D2" to the left or to the right.
Data
D1
Shift
D2
Reset
Starts the master control program.
(MC n)
Master control area
Ends the master control program.
(MCE n)
The program jumps to the label instruction and
(JP
n)
continues from there.
continues from there.
(LBL n)
FPΣ
Steps
(* Note)
3 (4)
3 (4)
3 (4)
4 (5)
5
7
3 (4)
5
1
5
2
2
2
1