Specifications
Item
No.
Name
COM.
411
Unit No. setting
2 port
2 port
Communication mode setting
412
set-
ting
ting
Selection of modem connection
414
Communication format setting
415
Communication speed (Baud rate)
setting
418
Starting address for received buffer of
general (serial data) communication
mode
419
Buffer capacity setting for data re-
ceived of general (serial data) commu-
nication mode
Note
The communication format when using the PLC link is fixed at
the following settings:
the data length is 8 bits, odd parity, stop bit is 1.
The communication speed (baud rate) is fixed at 115,200 bps.
13 - 20
Default
Descriptions
value
1
1 to 99
Computer link Computer link
General communication
Disabled
Enabled/Disabled
Character bit:
Enter the settings for the various items.
8 bits,
Character bit: 7bits/8bits
Parity check:
Parity chk: none/with odd/with even
"with, odd"
Stop bit: 1bit/2bits
Stop bit: 1 bit
The following setting is valid only when the
communication mode specified by system
register 412 has been set to "General com-
munication".
End code (Terminator): CR/CR+LF/None
Start code (Header): STX not exist/STX
exist
9600 bps
2400 bps
4800 bps
9600 bps
19200 bps
38400 bps
57600 bps
115200 bps
2048
0 to 32764
2048
0 to 2048
FPΣ