speed signal" maybe caused.
If genset without oil pressure sensor, please don't select corresponding items.
5)
6)
If not select generator frequency in crank disconnect setting, controller will not collect and display the
relative power quantity (can be used in water pump set); if not select speed in crank disconnect setting,
the engine speed displayed in controller is calculated by generator signal.

8 PARAMETERS SETTING

Start the controller, then press
follows:
1
Set Parameters
2
Information
3
Language
4
Eventlog
5
Maintennance
Parameters Setting
When entered password interface, inputting ―0318‖ can set all parameter items in Table 10. If the
password is changed, only input the password same as controllers', can the parameter be set via PC
software. If there is need to set more parameters (e.g. voltage calibration; current calibration), please
contact the factory.
NOTES:
1) Please change the controller parameters when generator is in standby mode only (e. g. Crank disconnect
conditions selection, digital input setting, relay output setting, various delay), otherwise, shutdown and
other abnormal conditions may occurs.
2) Over voltage set value must be higher than under voltage set value, otherwise over voltage and under
voltage condition may occur simultaneously.
3) Over speed set value must be higher than under speed set value, otherwise over speed and under speed
condition may occur simultaneously.
4) Please set the generator frequency value as low as possible when cranking, in order to make the starter be
separated quickly as soon as possible.
5) Digital input 1~6 could not be set as same items; otherwise, there are abnormal functions. However, the
relay output 1~5 can be set as same items.
6) If need to shut down after cooling, please set any auxiliary input as "High Temperature Stop Input", then
connect this input port to GND or set "High Temperature Stop Input" action as "Cooling Stop".
Controller Information
1) LCD will display developing information like software version, issue date of the controller.
Note: In this interface, press
2) Language selection.
Chinese, English and Spanish can be optional.
3) LCD contrast control
HGM8140 Military Genset Controller
HGM8140 MILITARY GENSET CONTROLLER USER MANUAL
to enter into the parameters setting menu, menu items as
will display the digital inputs and relay outputs status.
Version 1.0
2016-12-07