Smartgen HGM8140 User Manual page 28

Genset controller
Hide thumbs Also See for HGM8140:
Table of Contents

Advertisement

No.
Items
83
Custom Theme
Note1: if ―high temperature inhibit‖ is configured, or set auxiliary input as ―inhibit high temperature stop‖ and this
input is active, when temperature is higher than the preset value, or high temperature alarm input is active, controller
will send warning signal only and not stop the unit.
Note2: if ―low oil pressure inhibit‖ is configured, or set auxiliary input as ―inhibit low oil pressure stop‖ and this input is
active, when oil pressure is lower than the preset value, or low oil pressure alarm input is active, controller will send
warning signal only and not stop the unit.
Note3: If default password (0318) isn't changed, it doesn't need to input when configuring parameters via PC
software; if the password is changed for the first time via PC software, it need to input password in password window.
Note4: Between input correct password and LCD back light haven't got dark, input parameter numbers can enter
parameter setting interface when enters ―Password Input‖ again.
Note5: In teeth configuration interface, configure teeth status and power large than 20Hz, press start key for auto
calculating teeth numbers and press confirm key for changing teeth numbers.
No.
Item
00
Not Used
01
Common Alarm
02
Energise to Stop
03
Idle Control
04
Preheat Control
05
Close Gen Output
06
Reserved
07
Open
08
Speed Raise Relay
09
Speed Drop Relay
10
Run Output
11
Fuel Pump Control
HGM8140 Military Genset Controller
HGM8140 MILITARY GENSET CONTROLLER USER MANUAL
Parameters
Defaults
(0-2)
0
Table 11 - Relay Output Port 1-4 Contents
Output port is deactivated when ―Not Used‖ is selected.
Include all shutdown alarms and warning alarms. When there is
warning alarm only, it is not self-lock; when a shutdown alarm
occurs, it is self-lock until the alarm is reset.
Suitable for genset with electromagnet and will active after ―stop
idle delay‖. It is deactivated when the ―ETS Solenoid delay‖
expires.
Used for engine which has idles. Close before starting and open in
warming up delay; Close during stop idle delay and open when
stop is completed.
Close before starting and open before power up.
When close time is 0, it's continuous output.
When close time is 0, it's disabled.
Close when the generator enters into Warming Up delay (close
time: warming up delay).
Close when the generator enters into Stop Idle delay/ Energized to
Stop delay (close time: Stop Idle delay).
Action when genset is normal running while deactivated when
engine speed is lower than the ―crank disconnect speed‖.
Close when fuel level is lower than the ―Fuel Pump On‖ value or
when low fuel level warning input is active; Open when fuel level is
higher than the ―Fuel Pump Off‖ and low fuel level warning input is
deactivated;
Version 1.0
Description
0: Default Theme; 1: OEM plant Theme;
2: terminal Users Theme;
Description
2016-12-07
Page 27 of 54