Wirings Connection; Hgm8140M Military Genset Controller Pannel - Smartgen HGM8140 User Manual

Genset controller
Hide thumbs Also See for HGM8140:
Table of Contents

Advertisement

6 WIRINGS CONNECTION

6.1 HGM8140M MILITARY GENSET CONTROLLER PANNEL

No.
Function
1
B-
2
B+
3
Emergency Stop
4
Fuel Relay Output
5
Start Relay Output
6
Aux. Output 1
7
Aux. Output 2
8
Aux. Output 3
9
Charger(D+)
10
Aux. Input 1
HGM8140 Military Genset Controller
HGM8140 MILITARY GENSET CONTROLLER USER MANUAL
Fig.2 – HGM8140M Controller Rear Panel
Table 8 - Terminal Wiring Connection Description
Cable Size
2
2.5mm
2
2.5mm
2
2.5mm
2
1.5mm
2
1.5mm
2
1.5mm
2
1.5mm
2
1.5mm
2
1.0mm
2
1.0mm
Version 1.0
Remarks
Connected with negative of starter battery
Connected with positive of starter battery. If wire
length is over 30m, better to double wires in parallel.
Max. 20A fuse is recommended.
Connect with B+ via emergency stop button.
B+ is supplied by 3 terminal, rated 16A
B+ is supplied by 3 terminal, rated 16A.
Connect with boost coil of starter.
B+ is supplied by 2 terminal, rated 7A
B+ is supplied by 2 terminal, rated 7A
B+ is supplied by 2 terminal, rated 7A
Connected with charger starter's D+ (WL)
terminals. Being hang up If there is no this terminal.
Grounding is
Setting items please to see
active (B-)
Table 12
2016-12-07
Page 18 of 54