9 SENSOR SETTING

1) When reselect sensors, the sensor curve will be transferred into the standard value. For example,
if temperature sensor is SGH (120° C resistor type), its sensor curve is SGH (120° C resistor type);
if select the SGD (120° C resistor type), the temperature sensor curve is SGD curve.
2) When there is difference between standard sensor curves and using sensor, user can select
―custom sensors‖ and then input custom sensor curve.
3) When input the sensor curve, X value (resistor) must be input from small to large, otherwise,
mistake occurs.
4) When sensor selected as ―Not Used‖, LCD displays temperature, pressure and fuel level as ―- - -―.
5) If there is no oil pressure sensor, but there is low oil pressure alarm switch, user must set the oil
pressure sensor as ―None‖, otherwise, maybe low oil pressure shutdown occurs.
6) The headmost or backmost values in the vertical coordinates can be set as same as below,
1Pa
2
1kgf/cm
1bar
1psi
HGM8140 Military Genset Controller
HGM8140 MILITARY GENSET CONTROLLER USER MANUAL
or
and
Table 15 - Common Unit Conversion Table
2
N/m
Pa
1
4
9.8x10
5
1x10
3
6.89x10