Smartgen HGM8140 User Manual page 17

Genset controller
Hide thumbs Also See for HGM8140:
Table of Contents

Advertisement

No.
Type
9
Gen Over Current
10
Fail to Start
Gen Over
11
Frequency
Gen Under
12
Frequency
13
No Power Supply
14
Low Fuel Level
15
Low Coolant Level
Temp. Sensor Open
16
Circuit
Oil Pressure Sensor
17
Open Circuit
18
Maintenance Due
Digital Input Alarm
19
Shutdown
20
Over Power
21
Reverse Power
ECU Alarm
22
Shutdown
HGM8140 Military Genset Controller
HGM8140 MILITARY GENSET CONTROLLER USER MANUAL
When controller detects the current value is higher than the set value
and the delay value is not 0, it will send stop signals and the
corresponding alarm information will be displayed on LCD.
If genset start failure within setting of start times, controller will send
stop signals and the corresponding alarm information will be displayed
on LCD.
When controller detects the frequency value is higher than the set
value, it will send stop signals and the corresponding alarm information
will be displayed on LCD.
When controller detects the frequency value is lower than the set value,
it will send stop signals and the corresponding alarm information will be
displayed on LCD.
When controller detects genset frequency is 0, it will initiate shutdown
alarm and corresponding alarm information will be displayed on LCD.
When controller detects fuel level value lower than the pre-set value
and the low fuel level input is enabled, controller send stop signals and
the corresponding alarm information will be displayed on LCD.
When controller detects low coolant level input is active, controller send
stop signals and the corresponding alarm information will be displayed
on LCD.
When controller detects sensor,which connected to temperature
sensor, is open circuit, it will send stop signals and the corresponding
alarm information will be displayed on LCD.
When controller detects sensor,which connected to oil pressure
sensor, is open circuit, it will send stop signals and the corresponding
alarm information will be displayed on LCD.
Maintenance type can be set as genset running time, or date. When
genset running time has exceeded the user setting maintenance time
or the current date is over the setting date, and the action is
―Shutdown‖, controller will initiate a warning alarm and the
corresponding alarm information will be displayed on LCD. Setting
maintenance parameter after filling in the password can restore
maintenance alarm.
When digit input port is selected as user-defined and it is set as
―Shutdown Alarm‖ and the input is enabled, it will initiate a shutdown
alarm and corresponding information will be displayed on the LCD.
When controller detects the power value (power is positive) is higher
than the max. set value and the action select ―shutdown‖, it will send
stop signals.
When controller detects the reverse power value (power is negative) is
higher than the max. set value and the action select ―shutdown‖, it will
send stop signals.
After engine start, controller receives data signals, via J1939, controller
send stop signals.
Version 1.0
Description
2016-12-07
Page 16 of 54