No.
Items
Pressure
66
Curve
Fuel Level Sensor
67
Curve
68
Poles
Temp.
69
Open Circuit Action
Oil
Pressure
70
Sensor
Circuit Action
Disconnect
71
Pressure Delay
72
Scheduled Run
73
Scheduled Period
74
Auto Start Inhibited
75
Auto Start Inhibited
76
Overload Action
77
Boot Screen
Maintenance
78
Password
79
Date Setting
Custom
80
Curve
81
Engine Type
SPN
Alarming
82
Version
HGM8140 Military Genset Controller
HGM8140 MILITARY GENSET CONTROLLER USER MANUAL
Parameters
Sensor
(0-12)
(0-7)
(2-64)
Sensor
(0-2)
Open
(0-2)
Oil
(0-20.0)s
(0-1)
(0-1)
(0-1)
(0-2)
(0-2)
(0-1)
(0-9999)
Controller's date setting
Sensor
(0-2)
(0-39)
(0-3)
Defaults
8
SGX , details to see Table 13.
3
SGD, details to see Table 13.
Number of generator poles, which can be
4
used to speed calculating for gens without
speed sensors.
1
0:Not used ; 1:Warn; 2:Shutdown
When disconnect conditions include oil
pressure and engine oil pressure is higher
1
than disconnect oil pressure delay, the
genset is regarded as start successfully and
starter will disconnect.
When crank disconnect condition conclude
oil pressure, if engine oil pressure and delay
0.0s
value exceed pre-set crank disconnect
values, genset start successfully and starter
will disconnect.
0
0: Disabled; 1:Enabled
Monthly, weekly and daylily can be optional,
0
Start time and duration time can be
adjusted.
0
0: Disabled; 1:Enabled
Monthly, weekly and daylily can be optional,
0
Prohibit start time and duration time can be
adjusted.
0 Not used; 1 Warn; 2 Shutdown;
When the power exceeds preset limit, and
1
the duration is greater than the delay value,
over power alarm is active. Both return
value and delay value can be set.
0: Disenable
0
Boot Interface delay can be adjusted
Password to enter into the maintenance
0
setting page.
0 Custom temperature sensor
1 Custom pressure sensor
2 Custom level sensor
0
Choose sensor which need to be set, input
every point (8 points need to be input)
resistance
current, voltage) of curve.
1
Conventional J1939 engine
1
Alarming Version 1
Version 1.0
2016-12-07
Description
1:Enable
and
corresponding
Page 26 of 54
value(or

Advertisement

Table of Contents