No.
Item
12
High Speed Control
13
Auto Mode
14
Trip and Stop
15
Audible Alarm
Heater Control
16
17
Fuel Output
18
Start Output
19
ECU Stop
20
ECU Power Supply
21
ECU Warning
22
ECU Shutdown
ECU
Communication
23
Failure
24
Reserved
25
Reserved
26
Reserved
27
Reserved
28
Reserved
29
Reserved
Custom Period 1
30
Custom Period 2
31
Custom Period 3
32
Custom Period 4
33
Custom Period 5
34
Custom Period 6
35
36
Custom Combined 1
37
Custom Combined 2
HGM8140 Military Genset Controller
HGM8140 MILITARY GENSET CONTROLLER USER MANUAL
Close when the generator enters into Warming Up delay while
open after cooling delay.
The controller is in automatic mode.
Output when shutdown alarms appeared.
When warning and shutdown alarms appear, audible alarm output
is fixed as 300s. When ―alarm mute‖ or any keys on the panel
configurable input port is active, it can remove the alarm.
Controlled by the upper or lower limit of temperature sensor.
Activate when genset start, and break off when waiting for stop
steady.
Genset output only in crank output status.
Apply for engine with electronic injection ECU, which is used for
controlling ECU shutdown.
Apply for engine with electronic injection ECU, which is used for
controlling ECU power supply.
It is indicate that ECU has sent a warning alarm signal.
It is indicate that ECU has sent a shutdown alarm signal.
It is indicate that controller cannot communicate with ECU.
Detailed function description please to see the following content.
Version 1.0
Description
2016-12-07
Page 28 of 54