Bus Bars Interconnection - GE TLE series 600 User Manual

600 and 800 kva 400vac ce s1
Table of Contents

Advertisement

5.7.2 Bus bars interconnection

WARNING !
All the bus bars interconnection must be performed by QUALIFIED SERVICE
PERSONNEL only.
TLE Series 600 - Bus bars interconnection
!
Use the dedicated conductor
termination compound.
Example: PENETROX E
manufactured by BURNDY
BOLT Size (mm): M10
Connection
L1 Inverter
L2 Inverter
L3 Inverter
L1 Rectifier
L2 Rectifier
L3 Rectifier
N - Neutral
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
Critical Power
Power Section cabinet
Detail showing bus bars interconnection
Fig. 5.7.2-1 TLE Series 600 – Bus bars interconnection
Torque Specifications
Description of connection
Interconnection L1 Inverter
Interconnection L2 Inverter
Interconnection L3 Inverter
Interconnection L1 Rectifier
Interconnection L1 Rectifier
Interconnection L1 Rectifier
Interconnection N - Neutral
In/Out Section cabinet
Bus bars interconnection
L1 Inverter
L2 Inverter
L3 Inverter
L1 Rectifier
L2 Rectifier
L3 Rectifier
N - Neutral
BOLT Torque (N-m): 40
1 Bus bar 60/10 x 270 mm
1 Bus bar 60/10 x 270 mm
1 Bus bar 60/10 x 270 mm
1 Bus bar 60/10 x 270 mm
1 Bus bar 60/10 x 270 mm
1 Bus bar 60/10 x 270 mm
1 Bus bar 100/10 x 270 mm
M10 Pre Fixed Nut
Bus Bar
M10 Flat Washer
M10 Spring Washer
M10x35 Bolt
Bus bars interconnection
User Manual TLE Series 600 & 800 CE S1
Page 40/146