8.1.3 Restore to normal operation after "System shutdown" with Load not supplied

WARNING !
Please check and ensure the conditions of the connected load are safe before
proceeding, as this procedure will result in the connection of power to the load
circuit(s).
NOTE !
Before performing this operation, make sure that the UPS is in the following status:
 "Q1 - UPS Output switch" MUST BE CLOSED.
 "External Battery Protections" MUST BE DISCONNECTED.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled
before starting this procedure.
View of the Synoptic Diagram after performed the
command "System shutdown" with LOAD NOT
SUPPLIED.
1. Restore the command "System shutdown".
Restore the command "System shutdown" through the
screen: Commands 1 / System shutdown / RESET.
 The Load is supplied by the Mains through the Automatic Bypass.
 Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start.
At the end of Rectifier Soft-start the LED 1 (Rectifier) remains lit.
The Synoptic Diagram must display the status
"LOAD SUPPLIED BY AUTOMATIC BYPASS".