NOTE !
To operationalize this function, in case that the UPS was provided with one or
more cards "P4 - Customer Interface", there must be on each card the following:
- Remove the cable short-circuiting terminals X2 / 1, 2 (see Fig. 5.11-3).
- Remove the Jumper JP2 (see Fig. 5.11-3).
10
8
9
7
5
6
3
4
2
1
21
19
20
18
16
17
14
15
13
12
Fig. 5.11-3 X2 terminal block and Jumper JP2 on the P4 – Customer Interface Board
When the "EPO - Emergency Power Off" has been activated, the system must be restored as
follows:
Realise the push-button "EPO - Emergency Power Off" (contact on XA / EPO-1, EPO-2 is closed
again).
Perform the "Inverter OFF" command from the screen:
Commands 1 / Inverter / OFF.
(see User Manual to Section 7.5).
In case of a Parallel System perform the "Inverter OFF" command from the
screen "Commands 1 / Inverter / OFF" of each unit connected on the Parallel Bus
and having its output switch "Q1 - UPS Output" closed.