GE TLE series 600 User Manual page 113

600 and 800 kva 400vac ce s1
Table of Contents

Advertisement

During the first commissioning TLE Series 600 & 800 requests a set-up of the UPS configuration
parameters presented in the following "Power-Up" screen.
Without such configuration it is not possible to continue with the commissioning procedure.
WARNING
The set-up of the UPS configuration parameters must be done only by QUALIFIED
AND TRAINED PERSONNEL
The set-up of mistaken values could compromise the integrity and reliability of the
UPS
.
UPS
Language
Date (dd.mm.yyyy)
Time (24h)
Input Frequency
Output Frequency
Inverter Voltage
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
Critical Power
!
.
This parameter allows the choice of language used to display the
information.
You can adjust the date of the real time clock existing in the UPS by the
means of this parameter.
The value you enter is thoroughly checked to be a correct date in the
format "dd.mm.yyyy".
You can adjust the time of the real time clock existing in the UPS by
means of this parameter.
The value you enter is thoroughly checked to be a correct time in the
format "hh.mm.ss".
The time is specified in 24-hour format.
Input frequency value (50 Hz / 60Hz).
Inverter output frequency value (50 Hz / 60Hz).
Output voltage PHASE/NEUTRAL of the inverter (220V / 230V / 240V).
Continue
Page 113/146
User Manual TLE Series 600 & 800 CE S1