Restore To Normal Operation After "Epo - Emergency Power Off" With Load Not Supplied - GE TLE series 600 User Manual

600 and 800 kva 400vac ce s1
Table of Contents

Advertisement

8.2.4 Restore to normal operation after "EPO - Emergency Power Off" with Load not
supplied
WARNING !
Please check and ensure the conditions of the connected load are safe before
proceeding, as this procedure will result in the connection of power to the load
circuit(s).
NOTE !
Before performing this operation, make sure that the UPS is in the following status:
 "Q1 - UPS Output switch" MUST BE CLOSED.
"External Battery Protections" MUST BE DISCONNECTED.
View
of
the
Synoptic
performed the command "EPO -Emergency
Power Off", with LOAD NOT SUPPLIED.
1. Restore the "EPO -Emergency Power Off" button.
Press "MUTE" key to reset Alarm and Acoustical Alarm.
LED ALARM remains lit.
2. Perform the "Inverter OFF" command.
Perform the "Inverter OFF" command from
the screen: Commands 1 / Inverter / OFF.
Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start.
At the end of Rectifier Soft-start the LED 1
(Rectifier) remains lit.
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
Critical Power
Diagram
after
Continue
Page 119/146
User Manual TLE Series 600 & 800 CE S1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tle series 800

Table of Contents