Code
RECTIFIER TRANSFORMER
4106
OVERTEMPERATURE
4110
RECTIFIER MAINS OUT OF TOLERANCE
4115
LOW BATTERY VOLTAGE
4116
HIGH BATTERY VOLTAGE
4117
BATTERY EARTH FAULT
4118
4121
4125
HIGH DC-LINK VOLTAGE
4126
4
LEG CONTROL SATURATION (Imax)
th
4130
TURN ON RECT. OR SHUTDOWN UPS
4140
RECTIFIER CONTROL FAILURE
4141
ISMAX DETECTION RECTIFIER
4142
RECTIFIER CURRENT MAX
BOOSTER/BATTERY CHARGER CURRENT
4143
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
Alarm
BATTERY FAULT
HIGH DC RIPPLE
MAX
Critical Power
The temperature sensor inside the input
transformer
overtemperature.
Only the alarm is given.
The Rectifier, when in an Off state, cannot start
as long as this condition persists.
Rectifier Mains Input is out of tolerance
(voltage, frequency or phase sequence).
The Battery has been discharged and reached
"stop operation" time-out (default 3 minutes),
and the Inverter will be shut down.
It will restart automatically only when the
Battery has recharged enough for a minimum
runtime.
Dangerous high DC Voltage caused inverter
shut-down.
Inverter restarts automatically after Battery
returns to floating voltage.
A leakage current to earth has been detected
on the DC circuit.
During battery test the voltage falls under the
critical level (depending setting parameters).
Battery test is stopped.
A high ripple is present in the battery voltage.
Detection of high voltage on the DC-link.
The rectifier, booster and inverter will switch off
for protection purposes.
The rectifier may only be switched on again if
the DC-Link's voltage value falls below 430V.
The current in the fourth leg has reached its
highest value.
Rectifier and Inverter are OFF.
The DC power supply is discharging the
Battery.
Rectifier must be restarted or Battery must be
disconnected in order to avoid damage.
Rectifier Voltage hasn't reached the set value
(probably fault on regulation loop).
LED Rectifier on control panel is blinking.
After 3 IS-Max condition within the time frame
specified in respective parameter, the Rectifier
remains shut-down.
Will cause immediate shut-down of the
Rectifier.
Based on the value inserted in the respective
parameter.
Detection
of
booster/battery charger.
The Booster/Battery charger and Inverter will
switch off for protection purposes.
Description
winding
indicates
maximum
current
User Manual TLE Series 600 & 800 CE S1
in
the
Page 83/146