BATTERY
Capacity
Recharge Mode
Float Voltage
Recharge Current
Stop Operation Time
Cells
NOTE !
The values indicated above, must be considered as standard values.
The actual programmed values must be the ones defined from the Battery
Manufacturer.
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
Critical Power
Ah capacity of the Battery.
Recharge type of the Battery
Normal
-
NiCd
-
Wet Lead Acid Boost
-
Voltage to maintain Battery Charging.
Float voltage = Number of battery cells x battery float voltage per cell.
Typical battery float voltage per cell (ask the battery manufacturer for
confirmation):
Sealed Battery (VRLA):
2.27Vdc for cell
240÷264 cells x 2.27Vdc = 545 ÷ 600Vdc
NiCd Battery without boost-charge:
1.41Vdc for cell
386÷424 cells x 1.41Vdc = 545 ÷ 600Vdc
NiCd Battery with boost-charge:
1.41 (1.55 boost-charge) Vdc for cell
386 cells x 1.41Vdc = 545 (600) Vdc
Open Battery without boost-charge:
2.23Vdc for cell
244÷268 cells x 2.23Vdc = 545 ÷ 600Vdc
Open Battery with boost-charge:
2.23 (2.35 boost-charge) Vdc for cell
244÷254 cells x 2.23Vdc = 545 (573) ÷ 566 (600) Vdc
Maximum Battery Recharge Current.
Max 20% of battery capacity (Ah).
Example: 600Ah – max. recharging current 120A.
Residual Battery Autonomy time before UPS forced shut-down.
Standard set 3 minutes.
Settable from 1 minute to autonomy time in minutes.
Number of cells of the Battery, see "Float voltage".
Example: 240 battery cells
40 blocks / 12Vdc Battery
-
80 blocks / 6Vdc Battery
-
240 blocks / 2Vdc Battery
-
Sealed Battery (VRLA), NiCd without boost-
charge and Open Battery without boost-
charge.
Nickel Cadmium Battery with boost-charge.
Open Battery with boost-charge.
►
Continue