9.2.1 Connector J1 – RJ45 8P8C
11
9
10
8
6
7
4
5
2
3
1
21
22
19
20
17
18
15
16
14
12
13
J1 - RJ45
Fig. 9.2.1-1 Connector J1 – RJ45 8P8C
J1 - RJ45
8
CNT_Cable RJ45-RS232_01
1
Fig. 9.2.1-2 RJ45 –RS232 adaptation cable
The connector J1 – RJ45 is enabled on
all the units of the Parallel System.

9.2.2 X1 terminal block - Output signals on voltage-free contacts

The Customer Interface board provides 6 voltage free relay contacts giving some UPS critical alarms
and operation mode.
These signals are available on terminal blocks X1. Max. rating terminals: 1mm
The meaning of the alarms on the free contacts in standard configuration (default) is the following:
X1 / 1, 2, 3
X1 / 4, 5, 6
X1 / 7, 8, 9
X1 / 12, 13, 14
X1 / 15, 16, 17
X1 / 18, 19, 20
In case different alarms or operating status are required, they can be configured on the same terminals
via software from the control panel.
The configuration can be changed in parameters mode by a trained operator using the appropriate
password.
NOTE !
The programmable signals on X1 will be disabled with Q1 open, with the exception of
the signals for "16 - MANUAL BYPASS ON" and "26 – EMERGENCY ON (EPO)".

9.2.3 X1 terminal block - Programmable input free contacts

Some programmable UPS functions (indicated in Section 9.2), can be activated by closing an external
contact, if connected, on:
X1 / 10, 21
X1 / 11, 22
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
Critical Power
Total remote management of the system using software
GE iUPSGuard, GE Data Protection or GE Service Software
for system protection and management of the UPS
systems.
Fig. 9.2.1-3 Connector J1 to PC with RJ45 –RS232 adaptation cable
(NO, C, NC)
MAINS FAILURE
(NO, C, NC)
LOAD ON INVERTER
(NO, C, NC)
STOP OPERATION
(NO, C, NC)
LOAD ON MAINS
(NO, C, NC)
GENERAL ALARM
(NO, C, NC)
BUZZER (ACOUSTIC ALARM)
User Input 1 (default = Not used)
User Input 2 (default = GENERATOR ON)
J1 - RS232
TLE Series 600 & 800 is supplied with an
1
6
2
7
adaptation cable for a serial port RS232 /
3
8
4
9
5
sub DB9 connection.
.
2
(def. Parameter RL=1)
(def. Parameter RL=3)
(def. Parameter RL=5)
(def. Parameter RL=2)
(def. Parameter RL=4)
(def. Parameter RL=6)
Page 138/146
User Manual TLE Series 600 & 800 CE S1