8.3.3 Reconnect a UPS unit to Redundant Parallel System

NOTE:
The Load is still powered by the other units supplying the parallel bus.
This UPS unit will be powered on and connected to the parallel bus in order to
share the Load with each other's.
The high speed bus cable connecting
connected or disconnected after the system has been powered on.
The bus terminals must be properly connected before powering the additional
unit.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled
before starting this procedure.
If IEMi option is available, make sure that IEMi Operation Mode is disabled before
starting this procedure.
Open the front door, of the Unit to reconnect, and make sure that:
All the connections to the input/output terminals or bus bars of the UPS have been made correctly.
The protection panels are fastened in their correct position.
The switch Q1 is open (Pos. O) and the "External Battery Protections" must be open (Pos. O).
1. Switch-ON the Mains voltage, on the Unit to reconnect, from the input distribution (both
Rectifier and bypass if separated).
At this stage the Electronic Power Supply and Control Panel are switched ON and the Buzzer sounds.
Press "MUTE" key to reset Acoustical Alarm.
LED ALARM remains lit.
Synoptic diagram of the unit to reconnect
2. Close "Q1 - UPS Output switch" (Pos. I) on the Unit to reconnect.
Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start.
At the end of Rectifier Soft-start the LED 1 (Rectifier) remains lit.
Synoptic diagram of the unit to reconnect
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
Critical Power
J1A - J2A and J1B - J2B
Synoptic diagram of other units
Synoptic diagram of other units
in any case cannot be
Continue ►
Page 128/146