GE TLE series 600 User Manual page 89

600 and 800 kva 400vac ce s1
Table of Contents

Advertisement

Code
4604
COMMAND IEMi ON
4605
COMMAND IEMi OFF
4606
eBoost/IEMi ACTIVATION ALLOWED
4607
eBoost/IEMi ACTIVATION INHIBITED
4609
eBoost INHIBITED - LOW LOAD
4699
BATTERY TEST IMPOSSIBLE
4763
REMOTE CONTROL ON
4764
REMOTE CONTROL OFF
4798
SERVICE KEY ACTIVATED
4799
SERVICE KEY DEACTIVATED
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
Critical Power
Message
Description
The IEMi Operation Mode function is enabled, and
according to the time program the UPS system will
run in IEMi Operation Mode.
The IEMi Operation Mode has been disabled or the
programmed time is expired.
eBoost/IEMi control signal has been cleared on the
Customer Interface Board (X1 - 11, 22).
Operating mode depends on scheduled activation
of the functions.
Customer Interface Board (X1 - 11, 22) received an
eBoost/IEMi control signal.
eBoost™ Operation Mode and IEMi Operation
Mode will be temporarily inhibited.
eBoost™ Operation Mode inhibited due to minimal
load not reached.
Automatic Battery Test is not possible due to:
No Mains Rectifier or Bypass.
-
Battery not fully charged.
-
Load is below 10% or above 80%.
-
Test is postponed for 1 week.
Inverter can be started or shut-down by remote
control.
Commands source can be chosen depending on
the value of parameter (Service only):
0 = Only local panel
1 = Only Remote Control
2 = Both
Inverter cannot be started or shut-down by remote
control.
Commands source can be chosen depending on
the value of parameter (Service only):
0 = Only local panel
1 = Only Remote Control
2 = Both
A valid Service Key has been entered.
It will no longer be requested in the next 6 hours.
The Service Key validity period has expired.
Page 89/146
User Manual TLE Series 600 & 800 CE S1