5.4

PLACE OF INSTALLATION

5.4.1 UPS location

NOTE !
UPS installation and connection must be performed by QUALIFIED SERVICE
PERSONNEL only.
If optional cabinets and accessories are included with the UPS, please refer to those
accompanying manuals for installation and operating instructions.
It is important to have a clean, dust-free environment provided with proper ventilation and air-
conditioning to keep the ambient temperature within the specified operating range.
The recommended air inlet temperature is from 20°C (68°F) to 25°C (77°F) (max. 40°C / 104°F).
Refer to Section 5.5.
Check for sufficient floor load capacity before installing the UPS and the Battery.
Refer to Section 5.1.1.
For Battery installation follow the local codes and the recommendation of the battery supplier.
NOTE !
Operation at temperatures higher than 25°C (77°F) will reduce battery life.
Potential consequences are explained in Section 11.1.4: read and understand them.
The TLE Series 600 & 800 UPS can radiate radio frequency energy.
Although some RFI (Radio Frequency Interference) filtering is inherent to the UPS there is no guarantee
that the UPS will not influence sensitive devices such as cameras and monitors that are positioned close
by.
If interference is expected, the UPS should be moved away from the sensitive equipment.
Positioning of the UPS TLE Series 600 & 800
Min.
20" / 500mm
TLE Series 600
Fig. 5.4.1-1 TLE Series 600 & 800 – Positioning of the UPS
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
Critical Power
Min.
20" / 500mm
TLE Series 800
The rear panel of the UPS may be
mounted flush to a wall or other
structure.
Clearance around the front of the
unit should be sufficient to enable
free passage of personnel with the
doors fully open, and to allow
sufficient airflow to the door vents.
To guarantee proper cooling air
exhaust,
the
recommended
minimum clearance between ceiling
and top of the UPS is 500mm (19.7").
A single-phase power outlet (230
Vac) should be provided near the
UPS for connection of power tools,
test
equipment
or
devices.
This outlet must be grounded.