8.3
PROCEDURES FOR TLE SERIES 600 & 800 PARALLEL SYSTEM
8.3.1 TLE Series 600 & 800 Parallel System start-up
WARNING !
Before proceeding to turn on the UPS system, ensure that the AC and DC external
isolators are OFF, and prevent their inadverted operation.
Ensure that the Output Load distribution can be powered and all the Output
Isolators are open.
This procedure must be performed for the first start-up following the installation, with the Parallel
System completely switched Off and not powered.
Open the front door on all UPS units and make sure that:
All the connections to the input/output terminals or bus bars of the UPS have been made correctly.
The safety screens are fixed in their position.
The switch "Q1 –UPS Output" is open (Pos. O) and the "External Battery Protections" must be open
(Pos. O).
Q1
Q1
UPS Output switch
LED ALARM
Command Inverter ON
Command
Module shutdown
Command
System shutdown
1. Switch-ON the Mains voltage, on all UPS units, from the input distribution (both Rectifier and
bypass if separated).
The UPS performs a "Self-test".
A successful termination of the tests will be indicated with Overall test
results "OK".
Commissioning cannot be continued should one or more tests result to
be negative. Please contact in this case your Service Centre.
At this stage the Electronic Power Supply and Control Panel are switched
ON and the Buzzer sounds.
Press "MUTE" key to reset Acoustical Alarm.
LED ALARM remains lit.
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
Critical Power
LEDs on Synoptic Diagram
LED 1
Rectifier
LED 2
Inverter
LED 3
Booster/ Battery charger
LED LOAD PROTECTED
Command Inverter OFF
Command
Module shutdown RESET
Command
System shutdown RESET
LED 4 Automatic Bypass
LED 5 LOAD on UPS
Continue ►