Code
4146
4TH LEG DRIVER FAILURE
4147
BATTERY CHARGER DRIVER FAILURE
4150
BOOSTER OVERTEMPERATURE
4151
4TH LEG OVERTEMPERATURE
4301
INVERTER FUSES
4304
K7 CLOSING FAILURE
4305
K7 OPENING FAILURE
INVERTER TRANSFORMER
4307
OVERTEMPERATURE
4308
DC FUSES FAILURE
4309
DRIVER FAILURE
4310
IGBT RECTIFIER DRIVER FAILURE
4311
BOOSTER DRIVER FAILURE
INVERTER VOLTAGE OUT
4312
4320
ISMAX DETECTION
4321
HIGH CURRENT SHARING
4340
INVERTER CONTROL FAILURE
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
Alarm
OF TOLERANCE
Critical Power
The Booster's driver indicates the presence of a
defect which switches the power off.
The Battery charger driver indicates a defect,
switching it off.
The temperature of the booster bridge exceeds
the machine's set limit or the coil's sensor is on.
The temperature of the 4
the machine's set limit.
The alarm signals an inverter outlet fuses fault,
causing it to switch off immediately.
It may only be manually switched on after the
alarm has ceased.
K7 not closed despite a closing command.
Signalled by auxiliary contact.
Load will be supplied by Mains.
K7 not open despite an opening command.
Signalled by auxiliary contact.
Load will be supplied by Mains.
The
temperature
Transformer indicates overtemperature.
Elapsed "stop operation" time, Inverter shut-
down.
With Mains OK, Load is transferred on Mains.
Blown input DC fuse(s) F1 of the Inverter.
Inverter cannot be started as long as present.
An abnormal condition has been detected on one
or more power modules of the Inverter
(temperature or overcurrent).
Inverter shut-down and cannot be started as
long as the alarm is present.
Indicates a failure on the driver board or the
Rectifier IGBT bridge.
The Rectifier is shut-down.
Driver Booster error signal.
Inverter Output Voltage is out of the tolerances (
10%).
Inverter is switched OFF.
Detection of Inverter Bridge (Is) current limit
causing the Inverter OFF and automatic re-start.
After 3 times the Inverter switches-Off, and it can
be restarted manually.
A high exchange current value is detected
between the UPS of the Parallel System.
The "Slave" oscillator is not in synchronized with
the Master; thus causing the shut-down of its
Inverter.
If after a restart the condition remains, the LED
inside the Inverter symbol on the panel will not
light up, indicating that this Inverter cannot
supply the Load anymore.
Description
leg's bridge exceeds
th
sensor
of
the
User Manual TLE Series 600 & 800 CE S1
Inverter
Page 84/146