Restore To Normal Operation After "Epo - Emergency Power Off" With Load Not Supplied - GE TLE series 600 User Manual

600 and 800 kva 400vac ce s1
Table of Contents

Advertisement

8.3.6 Restore to normal operation after "EPO - Emergency Power Off" with Load not
supplied
WARNING !
Please check and ensure the conditions of the connected load are safe before
proceeding, as this procedure will result in the connection of power to the load
circuit(s).
NOTE !
Before performing this operation, make sure that all units of the Parallel System are
in the following status:
 "Q1 - UPS Output switch" MUST BE CLOSED.
 "External Battery Protections" MUST BE DISCONNECTED.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled
before starting this procedure.
If IEMi option is available, make sure that IEMi Operation Mode is disabled before
starting this procedure.
View of the Synoptic Diagram, on all UPS
units, after performed the command "EPO -
Emergency Power Off", with LOAD NOT
SUPPLIED.
1. Restore the "EPO -Emergency Power Off" button.
 Press "MUTE" key to reset Alarm and Acoustical Alarm.
LED ALARM remains lit.
2. Perform the "Inverter OFF" command on all Units.
Perform the "Inverter OFF" command from the screen:
Commands 1 / Inverter / OFF.
 Rectifiers start automatically.
LEDs 1 (Rectifier) blinking, indicates Soft-start.
 After performed the "Inverter OFF" command on the last unit of the Parallel System, the output of all
Units connect to Automatic Bypass.
The Synoptic Diagram, on all UPS units, must display the status "LOAD SUPPLIED BY AUTOMATIC BYPASS".
Synoptic diagram of first unit
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
Critical Power
Synoptic diagram of other units
Continue ►
Page 133/146
User Manual TLE Series 600 & 800 CE S1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tle series 800

Table of Contents