GE TLE series 600 User Manual page 65

600 and 800 kva 400vac ce s1
Table of Contents

Advertisement

Final units, first and last, of a RPA Parallel System
On the two boards P13/P14 – IM0222 – Bus Interface Board, of the first and last units of a Parallel
System, the switches SW1-1/2/3/4/5/6 MUST BE IN POSITION ON (see Fig. 5.10.2-2).
Intermediate units of a RPA Parallel System
On the two boards P13/P14 – IM0222 – Bus Interface Board, of the intermediate units of a Parallel
System, the switches SW1-1/2/3/4/5/6 MUST BE IN POSITION OFF (see Fig. 5.10.2-3).
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
Critical Power
J1B/1
J1A/1
Fig. 5.10.2-2 Bus connection on first and last units
J1B/2÷5
J1B/1
J1A/2÷5
J1A/1
Fig. 5.10.2-3 Bus connection on intermediate units
J1
B
J2
SW1
J1
A
J2
J1
B
J2
SW1
J1
A
J2
User Manual TLE Series 600 & 800 CE S1
Page 65/146