NOTE !
The UPS needs the connection of the Neutral at the input Bus Bars.
When the TLE Series 600 & 800 is utilized for different output frequency compared to the input
frequency, the Automatic Bypass and Manual Bypass (only if provided by customer) functions are
disabled, therefore the Load cannot be transferred to Mains in case of overload, short circuit, or inverter
failure.
In situations where the UPS needs to be powered down for maintenance purposes, the critical Load
must also be powered down during this time.
When the set-up parameters of the UPS are set for frequency converter, the eBoost™ Operation Mode
is automatically disabled.
Q1
TLE Series 600
Q1
TLE Series 800
Fig. 5.9.6-1 TLE Series 600 & 800 - Power connection for UPS utilized as frequency converter
In order to avoid improper operation, only the Rectifier input should be powered (L1-1, L2-1 and L3-1
/ Fig. 5.9.1-1 and Fig. 5.9.3-1), therefore BR1, BR2 and BR3, on the input bus bars MUST BE REMOVED
(see Fig. 5.9.2-2 and Fig. 5.9.4-2).
Special care must be taken in choosing the Fuse Ratings installed in the output distribution (max.
20% of the UPS rated current).
Avoid high inrush current due to transformer magnetisation or motor starting.
NOTE !
At site only a QUALIFIED SERVICE ENGINEER may change a unit, initially delivered
as a Frequency Converter, into a normally operating "standard" UPS.
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
!
INTERCONNECTIONS LINKS
BR1, BR2 and BR3
MUST BE REMOVED
(see Fig 5.9.2-2 and 5.9.4.2)
A
A
Critical Power
1
2
Rectifier
Bypass
Mains
Mains
Load
L3
L3-1
L3-2
Load
L2
L2-2
Load
L1
L1-2
N
Mains Neutral
Load Neutral
L2-1
PE
N
Mains Neutral
Load Neutral
L1-1
User Manual TLE Series 600 & 800 CE S1
Page 62/146

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tle series 800

Table of Contents