GE TLE series 600 User Manual page 79

600 and 800 kva 400vac ce s1
Table of Contents

Advertisement

Active power
Apparent power
Power factor
Status
Apparent power
Active Power
Overload counter
Inverter operating time
UPS operation time
eBoost operation time
IEMi operation time
Voltage DC-link 2
Status
Temperature
Temperature a / b / c / d
Modifications reserved
GE_UPS_OPM_TLE_SCE_M60_M80_1GB_V020.docx
Critical Power
Load active power (kW) for each phase.
Load apparent power (kVA) for each phase.
Load power factor: + inductive load / - capacitive load
Source of the power supplied to the Load.
Total apparent Load power (kVA).
Total effective Load power (kW).
Total number of detected output overloads.
Total operating time for the Inverter (in hours).
Total operating time for the UPS (in hours).
Total operating time for the UPS in eBoost™ Operation Mode (in hours).
This counter is displayed only when eBoost™ Operation Mode is available
(option).
Total operating time for the UPS in IEMi Operation Mode (in hours).
This counter is displayed only when IEMi Operation Mode is available (option).
DC-link 2 voltage.
Booster status (Off / Booster / Charger).
Temperature of the 4
a- Booster temperature (lower left module).
b- Booster temperature (upper left module).
c- Booster temperature (lower right module).
d- Booster temperature (upper right module – only for 800 kVA).
LOAD SCREEN
Voltage L1 / L2 / L3
Output voltage PHASE/NEUTRAL for each
phase.
Current L1 / L2 / L3
The output current as RMS values for
each phase.
Percent load L1 / L2 / L3
The output Load as percentage for each
phase.
BOOSTER SCREEN
Battery voltage
The battery voltage.
Battery current
The battery current (negative values
correspond to the discharge of the
battery).
Voltage DC-link 1
DC-link 1 voltage.
leg's bridge.
th
Page 79/146
User Manual TLE Series 600 & 800 CE S1