Resetting V7 EtherNet/IP Option Kit to its Default

The factory default settings:
Configure Network Parameters: DHCP
IP Address:192.168.1.20
Subnet: 255.255.255.0
Gateway: 192.168.1.1
Gateway Usage: Disabled
Symptom: The V7 EtherNet/IP Option Kit main web page does not display on the PC web browser screen.
Corrective Action: Check that the PC is setup, properly connected and that an IP address has been assigned to both the node and DHCP
server and that they are both on the same local network.
If the web page is still not visible after confirming PC setup, then reset the IP configuration of the V7 EtherNet/IP Option Kit to its factory
default as follows:
1.
Remove power from the V7 drive and wait for the charge lamp to be completely extinguished. Wait at least five additional minutes for
the V7 to be completely discharged. Measure the DC bus voltage and verify that it is at a safe level.
2.
Slide the bottom Load Defaults (LD) switch (SW1) to the ON position.
3.
Reapply power to the V7 and wait approximately 10 seconds for the power-up cycle to complete.
4.
Note: Additional wait time (approximately 2 minutes) may be required if utilizing the DHCP feature of this card, and the DHCP server
is not available, or it did not respond to the request for an IP address. The V7 EtherNet/IP Option Kit will indicate that the load defaults
process is complete when the MS/RUN LED is displaying a steady GREEN status indication after the wait time.
5.
Remove power from the V7 and wait for the charge lamp to be completely extinguished. Wait at least five additional minutes for the V7
to be completely discharged. Measure the DC bus voltage and verify that it is at a safe level. See the warning above.
6.
Slide the bottom Load Defaults (LD) switch (SW1) to the OFF position.
7.
Reapply power to the V7 and wait approximately 10 seconds for the power-up cycle to complete.
Fig 1.9 – EtherNet/IP Option Kit Reset Switch
Dangerous voltages in excess of 400VDC (230V drives) or 800VDC
(460V drives) are present at the DC bus terminals of the drive.
Installation 1-15
WARNING!