YASKAWA CIMR-V7AM Technical Manual page 18

V7 ethernet/ip option cm093
Table of Contents

Advertisement

Finish the V7 EtherNet/IP Option Kit Installation
1.
Remove power from the AC drive and wait for the charge lamp to be completely extinguished. Wait at least five additional minutes for
the drive to be completely discharged. Measure the AC drive DC bus voltage and verify that it is at a safe level.
2.
Reinstall all drive covers and the operator keypad. Apply power to the drive.
3.
Set parameters n003 and n004 to their appropriate values.
4.
Refer to the table below for available n003 and n004 values.
Addr
Drive Param
103h
n003
104h
n004
198h
n152
1
Note:
RS485 communications is disabled with the V7 EtherNet/IP Option Kit installed.
Dangerous voltages in excess of 400VDC (230V drives) or 800VDC
(460V drives) are present at the DC bus terminals of the drive.
Table 1.5 Reference and Operation Source Selection
Function
Data
0
1
Operation Method
Selection
2
3
0
1
2
3
4
Reference Selection
5
6
7
8
9
0
1
Display
Scaling
2-39
40-3999
WARNING!
Operator keypad
Terminal
1
Serial Communication
Option kit (V7 EtherNet/IP Option CM093)
Operator keypad potentiometer
Operator keypad
Voltage Reference (0-10VDC)
Current Reference (4-20mA)
Current Reference (0-20mA)
Pulse Train Reference
1
Serial Communication
Multi-Function Analog Input (0-10VDC)
Multi-Function Analog Input (4-20mA)
Option kit (V7 EtherNet/IP Option CM093)
0.01 Hz
0.1 %
RPM (Enter motor poles)
User Setting
Installation 1-13
Description
Default
Setting
1
2
0