Warning words 1+2 and Alarm word

Warning word, extended status word and alarm word
are shown in Hex format on the display. If there
is more than one warning or alarm, a sum of the
total warnings or alarms will be shown.
The descriptions relating to the extended status word
can be seen from in Status word as per FC protocol,
and with respect to warning word, extended status
word and alarm word, the descriptions can also be
read out via the serial bus in parameter 531 Warning
word, 532 Extended status word and 529 Alarm word.
Hex code
Extended status word
00000001
Overvoltage control active
00000002
Start delay
00000004
Sleep boost active
00000008
Sleep mode active
00000010
Automatic motor adaptation
completed
00000020
Automatic motor adaptation
running
00000040
Reversing and start
00000080
Ramp operation
00000100
Reversing
00000200
Speed = reference
00000400
Running
00000800
Local ref. = 1,
Remote controlled ref. = 0
00001000
OFF mode = 1
00002000
Auto mode = 0, Hand mode = 1
00004000
Start blocked
00008000
Start blocked signal missing
00010000
Freeze output
00020000
Freeze output blocked
00040000
Jogging
00080000
Jog blocked
00100000
Stand by
00200000
Stop
00400000
DC stop
00800000
Drive ready
01000000
Relay 123 active
02000000
Drive ready
04000000
Control ready
08000000
Start prevented
10000000
Profibus OFF3 active
20000000
Profibus OFF2 active
40000000
Profibus OFF1 active
80000000
Reserved
Hex code
00000010
Dry run
MG.83.A2.02 - VLT is a registered Danfoss trademark
Warning word 2
®
VLT
8000 AQUA
Hex code
00000001
Reference high
00000002
Fault in EEprom on control card
00000004
Fault in EEprom on power card
00000008
HPFB bus timeout
00000010
Serial communication timeout
00000020
Overcurrent
00000040
Current limit
00000080
Motor thermistor
00000100
Motor overtemperature
00000200
Inverter overtemperature
00000400
Undervoltage
00000800
Overvoltage
00001000
Voltage warning low
00002000
Voltage warning high
00004000
Mains failure
00008000
Live zero fault
00010000
Under 10 Volt (terminal 50)
00020000
Reference low
00040000
Feedback high
00080000
Feedback low
00100000
Output current high
00200000
Out of frequency range
00400000
Profibus communication fault
00800000
Output current low
01000000
Output frequency high
02000000
Output frequency low
04000000
AMA - motor too small
08000000
AMA - motor too big
10000000
AMA - check par. 102, 103, 105
20000000
AMA - check par. 102, 104, 106
40000000
Reserved
80000000
Reserved
Bit (Hex)
0000 0001
Unknown alarm
0000 0002
Trip locked
0000 0004
Automatic motor adaption fault
0000 0008
HPFB seriel communication
timeout
0000 0010
Basic serial communication
timeout
0000 0020
Short circuit
0000 0040
Switch mode fault
0000 0080
Earth fault
0000 0100
Over current
0000 0200
Current limit
0000 0400
Motor thermistor
0000 0800
Motor overload
0000 1000
Inverter overload
0000 2000
Under voltage
0000 4000
Over voltage
0000 8000
Mains imbalance
0001 0000
Live zero fault
0002 0000
Heat sink temperature too high
0004 0000
Motor phase W missing
0008 0000
Motor phase V missing
0010 0000
Motor phase U missing
0020 0000
HPFB seriel communication fault
0040 0000
Gate drive fault
0080 0000
Output current low
0100 0000
Safety interlock
0200 0000
Reserved
0400 0000
Dry run
(Remaining bits reserved for future use)
Warning word
Alarm word
167