LC filters VLT 8006-8011 380 - 480 V
Installation of LC filter IP 20
20
®
VLT
8000 AQUA
The drawing on the left gives the measurements of IP
20 LC filters for the above-mentioned power range.
Min. space above and under enclosure: 100 mm.
IP 20 LC filters have been designed for side-by-side
installation without any space between enclosures.
Max. motor cable length:
- 150 m screened/armoured cable
- 300 m unscreened/unarmoured cable
If EMC standards are to be complied with:
EN 55011-1B: Max. 50 screened/armoured
cable
EN 55011-1A: Max. 150 m screened/armoured
cable
Weight:
175Z0832
MG.83.A2.02 - VLT is a registered Danfoss trademark
9.5 kg