Technical data, mains supply 3 x 380 - 480 V

According to international requirements
1. For type of fuse, see section Fuses.
2. American Wire Gauge.
3. Measured using 30 m/100 ft screened motor cables at rated load and rated frequency.
4. Max. cable cross section is the maximum possible cable cross section that can be fitted on the terminals.
Always comply with national and local regulations on min. cable cross-section.
38
Output current
Output power
Typical shaft output
Typical shaft output
Max. cable cross-section
to motor
Max. input current
(RMS)
Max. cable
cross-section power
Max. pre-fuses
3)
Efficiency
Weight IP 20/NEMA 1
Weight IP 54/NEMA 12
Power loss at
max. load. [W]
Enclosure
®
VLT
VLT type
8006
I
[A] (380-440 V)
10.0
VLT,N
I
(60 s) [A]
VLT, MAX
11.0
(380-440 V)
I
[A] (441-480 V)
8.2
VLT, N
I
(60 s) [A]
VLT, MAX
9.0
(441-480 V)
S
[kVA] (400 V)
7.2
VLT,N
S
[kVA] (460 V)
6.5
VLT,N
P
[kW]
4.0
VLT,N
P
[HP]
5
VLT,N
2
2) 4)
[mm
]/[AWG]
4/10
I
[A] (380 V)
9.1
L,N
I
[A] (480 V)
8.3
L,N
2
2) 4)
[mm
]/[AWG]
4/10
1)
[-]/UL
[A]
25/20
0.96
[kg/lbs]
10.5/23
[kg/lbs]
14/31
Total
198
VLT type
IP 20/NEMA 1/IP 54/NEMA 12
MG.83.A2.02 - VLT is a registered Danfoss trademark
8000 AQUA
8008
8011
13.0
16.0
14.3
17.6
11.0
14.0
12.1
15.4
9.3
11.5
8.8
11.2
5.5
7.5
7.5
10
4/10
4/10
12.2
15.0
10.6
14.0
4/10
4/10
25/25
35/30
0.96
0.96
10.5/23
10.5/23
14/31
14/31
250
295