Relay Outputs - Danfoss VLT 8000 AQUA series Operating Instructions Manual

Hide thumbs Also See for VLT 8000 AQUA series:
Table of Contents

Advertisement

322 Terminal 45, output, pulse scaling
(AO 45 PULS SCALE)
Value:
1 - 32000 Hz
Function:
This parameter allows scaling of the pulse output signal.

Relay outputs

Relay outputs Relay outputs 1 and 2 can be used to give the present status or a warning.
Relay 1
1 - 3 break, 1 - 2 make
Max. 240 V AC, 2 Amp.
The relay is placed with
mains and motor terminals.
Relay Outputs
Value:
No function (NO FUNCTION)
Ready signal (READY)
Standby (STAND BY)
Running (RUNNING)
Running at ref. value (RUNNING AT REFERENCE)
Running, no warning (RUNNING NO WARNING)
Local reference active (DRIVE IN LOCAL REF)
Remote references active (DRIVE IN REMOTE REF.)
Alarm (ALARM)
Alarm or warning (ALARM OR WARNING)
No alarm (NO ALARM)
Current limit (CURRENT LIMIT)
Safety interlock (SAFETY INTERLOCK)
Start command active (START SIGNAL APPLIED)
Reversing (RUNNING IN REVERSE)
Thermal warning (THERMAL WARNING)
Hand mode active (DRIVE IN HAND MODE)
Auto mode active (DRIVE IN AUTO MODE)
Sleep mode (SLEEP MODE)
Output frequency lower than f
Output frequency higher than f
Out of frequency range (FREQ RANGE WARN.)
Output current lower than I
Output current higher than I
Out of current range (CURRENT RANGE WARN.)
Out of feedback range (FEEDBACK RANGE WARN.)
Out of reference range (REFERENCE RANGE WARN.)
Relay 123 (RELAY 123)
Mains imbalance (MAINS IMBALANCE)
Control word 11/12 (CONTROL WORD 11/12)
Motor alteration (MOTOR ALTERATION)
Function:
Description of choice:
See description of [0] - [28] in Analog/digital outputs.
= factory setting. () = display text [] = value for use in communication via serial communication port
128
5000 Hz
terminal no.
parameter
parameter 223 (F OUT < F LOW)
LOW
parameter 224 (F OUT > F HIGH)
HIGH
parameter 221 (I OUT < I LOW)
LOW
parameter 222 (I OUT > I HIGH)
HIGH
®
VLT
8000 AQUA
Description of choice:
Set the desired value.
Relay 2
4 - 5 make
Max. 50 V AC, 1 A, 60 VA.
Max. 75 V DC, 1 A 30 W.
The relay is placed on the control card, see
Electrical installation, control cables.
Control word bit 11/12. Relay 1 and relay 2 can
be activated via the serial communication. Bit 11
activates relay 1 and bit 12 activates relay 2.
MG.83.A2.02 - VLT is a registered Danfoss trademark
1
2
323
326
[0]
[0]
[1]
[1]
[2]
[2]
[3]
[3]
[4]
[4]
[5]
[5]
[6]
[6]
[7]
[7]
[8]
[8]
[9]
[9]
[10]
[10]
[11]
[11]
[12]
[12]
[13]
[13]
[14]
[14]
[15]
[15]
[16]
[16]
[17]
[17]
[18]
[18]
[19]
[19]
[20]
[20]
[21]
[21]
[22]
[22]
[23]
[23]
[24]
[24]
[25]
[25]
[26]
[26]
[27]
[27]
[28]
[28]
[29]
[29]
[30]
[30]

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents