Peak voltage on motor

When a transistor in the inverter is opened,
the voltage across the motor increases by a
dU/dt ratio that depends on:
- the motor cable (type, cross-section, length
screened or unscreened)
- inductance
The natural induction causes an overshot U
motor voltage before it stabilises itself at a level which
depends on the voltage in the intermediate circuit. The
rise time and the peak voltage U
life of the motor. If the peak voltage is too high, motors
without phase coil insulation are the ones that will
primarily be affected. If the motor cable is short (a few
metres), the rise time and peak voltage are lower.
If the motor cable is long (100 m), the rise time
and peak voltage will increase.
If very small motors are used without phase coil
insulation, it is recommended to fit a LC filter
after the frequency converter.
Typical values for the rise time and peak voltage
U
are measured on the motor terminals
PEAK
between two phases.
To obtain approximate values for cable lengths
and voltages not mentioned below, use the
following rules of thumb:
1. Rise time increases/decreases proportionally with
cable length.
2. U
= DC link voltage x 1.9
PEAK
(DC link voltage = Mains voltage x 1.35).
3.
Data are measured according to IEC 60034-17.
Cable lengths are in metres/feet.
VLT 8006-8011 / 380-480 V
Mains
Cable
volt-
length
age
Rise time
0.5 µsec.
50m/164ft
500 V
1 µsec.
150m/492ft
500 V
0.6 µsec.
50m/164ft
380 V
150m/492ft
380 V
1.33
µsec.
MG.83.A2.02 - VLT is a registered Danfoss trademark
in the
PEAK
affect the service
PEAK
Peak
voltage
dU/dt
1230 V
1968 V/µsec.
1270 V
1270 V/µsec.
1000 V
1333 V/µsec.
1000 V
602 V/µsec.
®
VLT
8000 AQUA
VLT 8016-8122 / 380-480 V
Mains
Cable
volt-
length
age
Rise time
0.27 µsec.
32m/105ft
380 V
0.60 µsec.
70m/230ft
380 V
1.11 µsec.
132m/433ft
380 V
VLT 8152-8352 / 380-480 V
Mains
Cable
volt-
length
age
Rise time
70m/230ft
400 V
0.34
µsec.
VLT 8452-8652 / 380-480 V
Mains
Cable
volt-
length
age
Rise time
29m/95ft
500 V
0.71
µsec.
29m/95ft
400 V
0.61
µsec.
VLT 8002-8011 / 525-600 V
Mains
Cable
volt-
length
age
Rise time
0.36 µsec.
35m/115ft
600 V
VLT 8016-8072 / 525-600 V
Mains
Cable
volt-
length
age
Rise time
0.38 µsec.
35m/115ft
575 V
VLT 8052-8402 / 525-690 V
Cable
Mains
length
voltage
Rise time
0.59 µsec.
25m/82ft
690 V
0.66 µsec.
25m/82ft
575 V
1.72 µsec.
1)
25m/82ft
690 V
VLT 8502-8652 / 525-690 V
Cable
Mains
length
voltage
Rise time
0.57 µsec.
25m/82ft
690 V
0.25 µsec.
25m/82ft
575 V
1.13 µsec.
1)
25m/82ft
690 V
1) With Danfoss dU/dt filter.
Peak
voltage
dU/dt
950 V
2794 V/µsec.
950 V
1267 V/µsec.
950 V
685 V/µsec.
Peak
voltage
dU/dt
1040 V
2447 V/µsec.
Peak
voltage
dU/dt
1165 V
1389 V/µsec.
942 V
1233 V/µsec.
Peak
voltage
dU/dt
1360 V
3022 V/µsec.
Peak
voltage
dU/dt
1430 V
3011 V/µsec.
Peak
voltage
dU/dt
1425
1983 V/µsec.
1159
1428 V/µsec.
1329
640 V/µsec.
Peak
voltage
dU/dt
1540
2230 V/µsec.
2510 V/µsec.
1629
1149 V/µsec.