Table 8.2: Description of Alarm Word, Warning Word and Extended Status Word

The alarm words, warning words and extended status words can be read out via serial bus or
optional fieldbus for diagnosis. See also par. 16-90, 16-92 and 16-94.
WARNING 1
10 Volts low:
The 10 V voltage from terminal 50 on the con-
trol card is below 10 V.
Remove some of the load from terminal 50, as
the 10 V supply is overloaded. Max. 15 mA or
minimum 590 Ω.
WARNING/ALARM 2
Live zero error:
The signal on terminal 53 or 54 is less than
50% of the value set in par. 6-10, 6-12, 6-20,
or 6-22 respectively.
WARNING/ALARM 3
No motor:
No motor has been connected to the output of
the frequency converter.
Hex
Dec
Alarm Word
00000001
1
Brake Check
00000002
2
Pwr. Card Temp
00000004
4
Earth Fault
00000008
8
Ctrl.Card Temp
00000010
16
Ctrl. Word TO
00000020
32
Over Current
00000040
64
Torque Limit
00000080
128
Motor Th Over
00000100
256
Motor ETR Over
00000200
512
Inverter Overld.
00000400
1024
DC under Volt
00000800
2048
DC over Volt
00001000
4096
Short Circuit
00002000
8192
Inrush Fault
00004000
16384
Mains ph. Loss
00008000
32768
AMA Not OK
00010000
65536
Live Zero Error
00020000
131072
Internal Fault
00040000
262144
Brake Overload
00080000
524288
U phase Loss
00100000
1048576
V phase Loss
00200000
2097152
W phase Loss
00400000
4194304
Fieldbus Fault
00800000
8388608
24 V Supply Low 24V Supply Low
01000000
16777216
Mains Failure
02000000
33554432
1.8V Supply Low Current Limit
04000000
67108864
Brake Resistor
08000000
134217728
Brake IGBT
10000000
268435456
Option Change
20000000
536870912
Drive Initialised
40000000
1073741824
Safe Stop
®
MG.11.B2.02 - VLT
is a registered Danfoss trademark
Warning Word
Extended
Word
Brake Check
Ramping
Pwr. Card Temp
AMA Running
Earth Fault
Start CW/CCW
Ctrl.Card Temp
Slow Down
Ctrl. Word TO
Catch Up
Over Current
Feedback High
Torque Limit
Feedback Low
Motor Th Over
Output Current High
Motor ETR Over
Output Current Low
Inverter Overld.
Output Freq High
DC under Volt
Output Freq Low
DC over Volt
Brake Check OK
DC Voltage Low
Braking Max
DC Voltage High
Braking
Mains ph. Loss
Out of Speed Range
No Motor
OVC Active
Live Zero Error
10V Low
Brake Overload
Brake Resistor
Brake IGBT
Speed Limit
Fieldbus Fault
Mains Failure
Low Temp
Voltage Limit
Unused
Unused
Unused
WARNING/ALARM 4
Mains phase loss:
A phase is missing on the supply side, or the
mains voltage imbalance is too high.
This message also appears in case of a fault
in the input rectifier on the frequency convert-
er.
Check the supply voltage and supply currents
to the frequency converter.
WARNING 5
DC link voltage high:
The intermediate circuit voltage (DC) is higher
than the overvoltage limit of the control sys-
tem. The frequency converter is still active.
WARNING 6
DC link voltage low
The intermediate circuit voltage (DC) is below
the undervoltage limit of the control system.
The frequency converter is still active.
8. Troubleshooting