Troubleshooting

10.5 Alarm and Warning Words

PROFINET alarm words and warning words are shown on
the display in Hex format. If there is more than one
warning or alarm, a sum of all warnings or alarms will be
shown. Alarm word, warning word, and, PROFINET warning
word can also be displayed using the serial bus in
16-90 Alarm Word, 16-92 Warning Word and 9-53 Profibus
Warning Word.
Bit (Hex)
Unit
Alarm word (16-90 Alarm
diagnose
Word)
bit
00000001
48
Brake check
00000002
49
Power card over
temperature
00000004
50
Earth fault
00000008
51
Control card over
temperature
00000010
52
Control word timeout
00000020
53
Over current
00000040
54
Torque limit
00000080
55
Motor thermistor over
temp.
00000100
40
Motor ETR over
temperature
00000200
41
Inverter overloaded
00000400
42
DC link under voltage
00000800
43
DC link over voltage
00001000
44
Short circuit
00002000
45
Inrush fault
00004000
46
Mains phase loss
00008000
47
AMA not OK
00010000
32
Live zero error
00020000
33
Internal fault
00040000
34
Brake overload
00080000
35
Motor phase U is missing
00100000
36
Motor phase V is missing
00200000
37
Motor phase W is missing
00400000
38
Fieldbus comm. fault
00800000
39
24 V supply fault
01000000
24
Mains failure
02000000
25
1.8 V supply fault
04000000
26
Brake resistor short circuit
08000000
27
Brake chopper fault
10000000
28
Option change
20000000
29
Drive initialisation
40000000
30
Safe stop
80000000
31
Mechanical brake low
Table 10.16 FC 102/FC 202/FC 301/FC 302/FCD 302
MG90U302
Operating Instructions
Bit (Hex)
00000001
00000002
00000004
00000008
00000010
00000020
Alarm no.
00000040
00000080
28
00000100
29
00000200
14
00000400
65
00000800
00001000
18
00002000
13
00004000
12
00008000
11
00010000
00020000
10
00040000
00080000
9
00100000
8
00200000
7
00400000
16
00800000
33
01000000
4
02000000
50
04000000
2
08000000
38
10000000
26
20000000
30
40000000
31
80000000
32
34
47
Table 10.17 FC 102/FC 202/FC 301/FC 302/FCD 302
36
48
25
27
67
80
68
63
Danfoss A/S © Rev. 2014-02-27 All rights reserved.
Unit
Warning word
diagnose
(16-92 Warning Word)
bit
112
Brake check
113
Power card over
temperature
114
Earth fault
115
Control card
116
Control word timeout
117
Over current
118
Torque limit
119
Motor thermistor over
temp.
104
Motor ETR over
temperature
105
Inverter overloaded
106
DC link under voltage
107
DC link over voltage
108
DC link voltage low
109
DC link voltage high
110
Mains phase loss
111
No motor
96
Live zero error
97
10 V low
98
Brake overload
99
Brake resistor short circuit
100
Brake chopper fault
101
Speed limit
102
Fieldbus comm. fault
103
24 V supply fault
88
Mains failure
89
Current limit
90
Low temperature
91
Voltage limit
92
Encoder loss
93
Output frequency limit
94
Unused
95
Warning word 2 (ext. stat.
word)
Alarm no.
28
29
14
65
18
13
12
11
10
9
8
7
6
5
4
3
2
1
26
25
10
10
27
49
34
47
36
59
66
64
61
62
-
-
67

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents