JFWSG FlashScan Wireless System Gateway

Activating the Profile Magnetic Sensor

Activating the profile magnetic sensor (refer to Figure 2.2) when the gateway has a profile will put
the gateway in a mode of distributing the profile to any device that requests a profile. The gate-
way's LED pattern will be altered when it is distributing a profile for easy identification. Profile
distribution will automatically terminate after 10 minutes. For more information on gateway LED
patterns, refer to Section 2.5 on page 12.
2.8.4 SLC Configuration
The gateway:
communicates with the control panel via the SLC.
is a FlashScan-only device.
does not support CLIP mode.
is only compatible with FACPs version 24 or higher.
occupies one module SLC address. Set the address using the rotary dials on the gateway
prior to installation.
The SLC point uses the following configuration parameters:
Module Type: Monitor
Type Code Label: RF GATEWAY
FlashScan Type: RF GATEWAY
A gateway does not initiate alarms but the point is used for event reporting.

2.9 Operations

2.9.1 Modes of Operation
Factory
Default
22
SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000JC-E:C 5/8/2015
6 7
8 9
10
5
11
4
12
3
13
2
1
14
0
15
TENS
Figure 2.14 Address Rotary Switches
Start-up
Mesh
Profile
Formation
Configured
Figure 2.15 Gateway Modes Of Operation
6 7
8 9
5
4
3
2
1
0
ONES
Restructuring
Initial Mesh
Restructuring
Rescue
Fire Protection Provided
Operations
Mesh
Normal
Mode
Mode