Assign A Previously Created Profile Using A Distributor; Remove A Profile; Create A Mesh Network - Johnson Controls SWIFT Instruction Manual

Smart wireless integrated fire technology
Table of Contents

Advertisement

JFWSG FlashScan Wireless System Gateway
1.
Start with the gateway powered off. The profile creation process is performed during start-up.
2.
Power on the gateway using SLC power or external +24V. Refer to Sections 2.7.3 and 2.7.4 for
more information.
3.
Ensure that the gateway is in the factory default state. If the gateway is in the factory default
state, both the LEDs on the gateway will double blink red every second for ten seconds. If the
LEDs are yellow, refer to "Remove a Profile" on page 18.
4.
Activate either magnetic sensor with a magnet within ten seconds of starting up the gateway
while the double red blink is active on the gateway. Refer to Section 2.4, "Magnet Sensors" for
further information on activating magnetic sensors. The LED next to the magnetic sensor emits
a red light for one second when it is activated. If the ten second window is missed, power
down the gateway and repeat the process starting at step 1.
A profile has been created successfully; the LEDs on the gateway will light green and stay on
steady for ten seconds. The profile has been created containing a mesh ID and a default password.
The default password is '12345' and is needed if the gateway is locked by the FACP and later
accessed by SWIFT Tools.
Immediately after successful profile creation, the gateway starts the profile distribution mode.
Refer to Section 2.8.3 for further information on profile distribution mode.

Assign a Previously Created Profile Using a Distributor

Instead of creating a new profile, an existing profile can be distributed by a device with an existing
profile. To distribute the existing profile:
1.
Ensure that the gateway or other mesh device with the profile is set for distribution. Refer to
Section 2.8.3, "Profile Distribution" or Section 3.5.2, "Distributor Mode".
2.
Bring the profile distributor within 20 feet of the gateway.
3.
10 seconds after the initial start-up, the LEDs on the gateway switch from a double red blink to
a single red blink. The single red blink indicated the gateway is ready.
4.
Use a magnet to activate either of the magnetic sensors. The LED will blink a single red every
half-second indicating that it is searching for a profile.
When the profile is successfully received from the distributor, the LEDs on the gateway will turn
on green steady for five seconds.

Remove a Profile

To remove a profile from a gateway:
1.
Start with the gateway powered off. The process is performed during start-up.
2.
Power on the gateway using SLC power or external +24V. Refer to Sections 2.7.3 and 2.7.4
for more information.
3.
Verify the gateway is in the profile modification state. The gateway is in the profile
modification state when both the LEDs on the gateway double blink yellow every second for
ten seconds.
4.
Activate both magnetic sensors on the gateway within ten seconds of start-up while the double
yellow blink is active. If the ten second window is missed, power down the gateway and repeat
the process starting at step 1.
The LEDs on the gateway will blink green every second for five seconds indicating that the profile
is removed.

Create a Mesh Network

The gateway communicates with all devices in range that have a common profile and establishes
communication links with all the devices. This creates a mesh network. Once a device joins the
mesh, that device acts as a repeater for devices out of the range of the gateway. All devices must be
18
SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000JC-E:C 5/8/2015
Configuration and Programming

Advertisement

Table of Contents
loading