Collapse Mesh Network at the Panel
To collapse the mesh network using the IFC2-3030 or JNCA-2 with IFC2-640 FACP, refer to the
"shutdown wireless" section of the IFC2-3030 or JNCA-2 Manual.
2.9.6 Silence Network Command
The silence network command is a diagnostic function to turn off all radio communication from the
wireless devices for a set amount of time. All devices will retain the profile information but will be
removed from the mesh. The devices will not send or receive any wireless communication until the
set time expires or the device is rebooted. The mesh network can be reformed at the end of the
silence period or after the device is restarted.
CAUTION: FIRE PROTECTION DISABLED
!
FIRE PROTECTION FROM WIRELESS DEVICES WILL BE DISABLED WHEN A SILENCE
COMMAND IS ISSUED.
The mesh network can be silenced using SWIFT Tools.
Silence Mesh Network Using SWIFT Tools
To silence the mesh network:
1.
Connect the W-USB dongle device to your computer. For more information on the USB
dongle, refer to Section 4.
2.
Launch the SWIFT Tools application. Refer to Appendix A, "SWIFT Tools" for more
information.
3.
From the Home Screen, select the Diagnostics function.
4.
Select a Gateway from the communicator panel.
5.
Click View Mesh. The mesh is displayed.
6.
Click Advanced Functions on top of the mesh display. A drop-down list is displayed.
7.
Click Silence Devices. The Silence mesh network screen is displayed.
8.
Select the time interval to silence the wireless devices from the dropdown list and click Yes.
28
SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000JC-E:C 5/8/2015
Figure 2.24 Advanced Functions Options
Figure 2.25 Silence Mesh Network Screen
Operations