Johnson Controls SWIFT Instruction Manual page 62

Smart wireless integrated fire technology
Table of Contents

Advertisement

LED Indicators
LED Pattern
Profile
modification
60
5
Solid
Battery Check: all
batteries present
2.5
Searching for mesh
(in rescue mode)
3
90
Searching for mesh
(in formation mode)
25
1st mesh
restructuring
M
5
7
Generic device trouble
(dual address, low
battery, etc.)
14
Solid
Tamper entry
4
Solid
Discovered mesh
6
Solid
Battery Check:
weak
2.5
Alarm state
3
Waiting for a profile
10
Searching for a profile
M
0.5
1
Pending site survey
5
Legend
All units are in seconds. Minute is indicated by "M".
62
SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000JC-E:C 5/8/2015
Device LED Patterns (Continued)
Condition
Device has a profile and
can be set as a distributor
or have profile removed.
Minimum of 6 months battery
life remaining.
Profile is assigned and device
is searching for the mesh.
Profile is assigned and device
is searching for the mesh.
Mesh is formed and
initializing.
Device is in the mesh and in
a trouble condition.
Device has just been
tampered.
Device discovered the
mesh.
Less than 6 months
battery life left or not all 4
batteries are present.
Device is functioning as
normal and has been
activated.
Device is in factory default
mode.
Device is in factory default
mode and requesting a profile
from a distributor or gateway.
Device is in factory default
mode and is ready to enter
site survey mode.
Number of blinks
LED color
Interval between blink patterns
Duration of LED state
Indicates value is approximate
Action Required
Toggle SLC address dials to
respective pattern to enter
desired mode.
Ensure the mesh is in rescue
mode or wait for timeout to search
mesh in formation mode.
Ensure the mesh is in formation
mode.
Refer to the FACP to identify the
trouble and possible resolution.
The IFC2-640/IFC-320 does not
support trouble indication.
Ensure detector is seated in the base
and the module has a faceplate.
Ensure all 4 batteries are present
or replace the batteries.
Use SWIFT Tools to assign a
profile or activate magnetic sensor
to search for a profile.
Clear the tamper condition within 1
minute to enter site survey mode.
Example:
Two blinks in this pattern
First blink is green. Second is yellow
M
7
20
7 seconds between blink patterns
Will transition to next state after
approximately 20 minutes

Advertisement

Table of Contents
loading

Table of Contents