LED Indicators
LED Pattern
Profile assigned;
pending magnetic
1
10
sensor activations
1st mesh
restructuring
M
7
5
1st mesh
restructuring with
profile distribution
M
7
5
Trouble
14
Trouble with
profile distribution
14
Address zero
trouble
4
Factory default;
pending magnetic
sensor activation
1
10
Waiting for a profile
10
Searching for a
profile
0.5
60
Create profile
1
Legend
Number of blinks
LED color
Interval between blink patterns
Duration of LED state
Indicates value is approximate
All units are in seconds. Minute is indicated by "M".
60
SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000JC-E:C 5/8/2015
Gateway LED Patterns (Continued)
Condition
Gateway is starting up with a
profile.
Mesh is formed and initializing.
Mesh is formed and initializing.
The gateway is also distributing a
profile to any device that requests
a profile.
The gateway has a trouble
condition.
The gateway has a trouble
condition. The gateway is also
distributing a profile to any device
that requests a profile.
The gateway address is set to zero.
Gateway is starting up without a
profile.
Gateway is in factory default mode.
Gateway is in factory default mode
and requesting a profile from a
distributor or another gateway.
Gateway is creating a profile.
Example:
M
7
20
Action Required
Activate both magnetic sensors
simultaneously within 10 seconds
to remove a profile.
Ensure all devices in the mesh
have a valid address.
Refer to the FACP to identify
the trouble and possible
solution.
Refer to the FACP to identify
the trouble and possible
solution.
Ensure all devices in the mesh
have a valid address.
Activate either magnetic sensor
within 10 seconds to create a
profile.
Use SWIFT Tools to assign a
profile or activate magnetic sensor
to search for a profile.
Two blinks in this pattern
First blink is green. Second is yellow
7 seconds between blink patterns
Will transition to next state after
approximately 20 minutes