Johnson Controls SWIFT Instruction Manual page 61

Smart wireless integrated fire technology
Table of Contents

Advertisement

LED Pattern
Bootloader
normal
Slot request
rejected
8
Mesh forming
M
7
20
Sustained tamper
15
Bootloader
firmware update
Profile removed
1
5
Solid
Profile received
10
Solid
Battery check: all
batteries are fresh
2.5
Distributor mode
0.5
Rescue mode
M
7
3
Normal mode
14
Solid
Self test fail
Low battery cut-off
1
Legend
All units are in seconds. Minute is indicated by "M".
SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000JC-E:C 5/8/2015
Device LED Patterns
Condition
Device is ready to update.
Device is not permitted
into the mesh.
Device is part of the mesh
and looking for devices that
are not in the mesh.
Device is tampered.
New application code is
being downloaded.
Device has returned to the
factory default mode.
Device is now profile
assigned.
Maximum life of installed
batteries remaining in
device
Device is distributing its
profile to other devices
which requested a profile.
Device is functioning as
normal and searching for
lost devices.
Device is distributing as
normal
Device has failed internal
self diagnostics.
Device is functioning.
Number of blinks
LED color
Interval between blink patterns
Duration of LED state
Indicates value is approximate
Action Required
Use SWIFT Tools to initiate
download.
Confirm device count and
software version.
Ensure detector is seated in the
base and the module has the
faceplate on.
Restart the device. If problem
persists, contact technical support.
Replace batteries.
Example:
Two blinks in this pattern
First blink is green. Second is yellow
M
20
7
7 seconds between blink patterns
Will transition to next state after
approximately 20 minutes