Assigning A Profile To A Device (Detector Or Module) Using A Gateway Or Distributor - Johnson Controls SWIFT Instruction Manual

Smart wireless integrated fire technology
Table of Contents

Advertisement

Configuration and Programming
Assigning a Profile to a Device (Detector or Module) Using a Gateway or
Distributor
A gateway that has a profile can be used to distribute that profile to other devices. The gateway
must be in distributor mode before it can distribute a profile. For more information on converting a
gateway to a distributor, refer to Section 2.8.3. A device with a profile can be used to distribute the
profile. To put a device into distributor mode, refer to topic, "Converting a Device into a Distribu-
tor" on page 37.
Distribute a Profile from a Gateway/Distributor to a Detector
To transfer a profile from a gateway/distributor to a detector:
1.
Bring the detector within 20 feet of the gateway/distributor.
2.
Power on the detector. Ensure the detector is in factory default state. The LED on the detector
will single-blink or double-blink red confirming that it is in the factory default state.
3.
Activate the magnet test switch shown in the figure below. Once the magnet sensor has been
activated, the LED blinks red every half second indicating that it is requesting a profile. If the
profile is successfully received, the green LED turns on steady for 10 seconds. If the profile is
not received within 1 minute, the LED blinks red every ten seconds indicating that it has
stopped requesting a profile.
Distribute a Profile from a Gateway/Distributor to a Module
To transfer a profile from a gateway/distributor to a module:
1.
Bring the detector within 20 feet of the gateway/distributor.
2.
Power on the module. Ensure the module is in factory default state. If the module is in factory
default state, the LED blinks red once.
3.
Toggle the state of the tamper condition to instruct the module to request a profile. To toggle
the tamper condition state, start with the faceplate removed.
4.
Quickly replace then remove the faceplate from the module. Do not attach the mounting
screws for the faceplate during this step. The LED blinks red every half second indicating that
it is requesting a profile. The green LEDs turn on steady for ten seconds indicating that the
profile has been assigned. If the profile is not received within 1 minute, the LED blinks red
every ten seconds indicating that it has stopped requesting a profile.
SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000JC-E:C 5/8/2015
LED
Tamper
magnet
Figure 3.1 Magnetic Sensor on a Detector
Wireless Devices
LED
Magnet test
switch
35