Mounting And Wiring; 1: Mounting - Johnson Controls SWIFT Instruction Manual

Smart wireless integrated fire technology
Table of Contents

Advertisement

Mounting and Wiring

2.7 Mounting and Wiring
WARNING: FORMEX SHEET
!
ENSURE THAT THE FORMEX SHEET INSIDE THE GATEWAY IS NOT REMOVED OR
TAMPERED WHILE INSTALLING OR CLEANING.
2.7.1 Mounting
The gateway has two major pieces, the cover and the mounting plate. The mounting plate is
mounted to the wall or ceiling, and field wiring is connected to it. The cover contains the printed
circuit board and is fastened to the mounting plate once the wiring is completed.
Mount the mounting plate directly to an electrical box on the ceiling or wall. The plate mounts
directly to a 4˝ square (with and without plaster ring), 4˝ octagon, 3 1/2˝octagon, single gang or
double gang junction boxes. If an electrical box is not available, the mounting plate can be mounted
to any flat surface and the wiring can be connected via the knockout points in the mounting plate.
To mount the gateway:
1.
Pull the wiring through the opening in the mounting plate.
2.
Mount the mounting plate to the junction box or ceiling. See Figure 2.3 below.
3.
Connect field wiring to the terminals, as described in Section 2.7.2.
4.
Connect necessary jumpers where applicable, as described in Section 2.7.3.
5.
To mount the cover, align the locating pins on the cover to the corresponding slots in the
mounting plate. See Figure 2.4.
6.
Secure the cover by tightening the mounting screws.
locating pin
SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000JC-E:C 5/8/2015
locating pin
Figure 2.3 Mounting Plate for Wireless Gateway
JFWSG FlashScan Wireless System Gateway
locating pin
13