9: Trouble Messages - Johnson Controls SWIFT Instruction Manual

Smart wireless integrated fire technology
Table of Contents

Advertisement

JFWSG FlashScan Wireless System Gateway
2.9.9 Trouble Messages
IFC2-3030
IFC2-640
JNCA-2
IFC-320
IFI
RADIO JAMMING
JAM
INCOMPAT SOFT
IN SFT
MESH IS
MS FRM
FORMING
MESH NOT
NOMESH
FORMED
RESTRUCTURING
RSTRCT
PROFILE MISSING PR MIS
NO WIRELESS
NO DEV
DEVS
ADDRESS FAULT
ADRFLT
MAX GATEWAYS
MAX GW
30
SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000JC-E:C 5/8/2015
Type
Description
Non-latching
The gateway is being
overloaded with RF energy
and is unable to receive
messages from other
devices.
Non-latching
Software mismatch
between the application
code for the RF processor
and the SLC processor.
Non-latching
The gateway and attached
devices are searching for
additional devices to join
the mesh. The wireless
system is not able to
provide fire protection
during this time.
Non-latching
The gateway contains a
profile but has not formed a
mesh.
Non-latching
The gateway is performing
the initial identification and
assignment of optimal
communication paths for
the mesh network. The
wireless system is not able
to provide fire protection
during this time.
Non-latching
The gateway is in the
factory default state and is
not providing fire
protection.
Non-latching
The gateway is functional
but is not in communication
with any wireless devices.
Non-latching
There is either a device in
the mesh set to address 0
or there is a duplicate
address used for another
wireless module at the
address of the gateway.
Non-latching
Wireless communication
reliability is compromised
due to the installation limits
of JCI wireless systems
being exceeded.
Table 2.1 Trouble Messages
Course of Action
Identify any RF emitters in close proximity
of the gateway and remove them or
relocate the gateway.
Use SWIFT Tools to identify the mismatch,
and update the processors as necessary
for compatibility.
Wait until all desired wireless devices are
communicating and are members of the
mesh network. Once all desired devices
are in the mesh network, the mesh forming
mode can be terminated by the user by
activating the Mesh formation magnetic
sensor or by using the SWIFT Tools. If no
action is taken, this mode will
automatically exit 10 minutes after the last
device joins.
To form a mesh, refer to, "Create a Mesh
Network".
No action needed. The duration of this
event correlates to the number of devices
in the mesh. A fully loaded mesh may take
up to 5 minutes to restructure.
A profile needs to be created or assigned
to the gateway before a mesh can be
formed.
Verify the desired wireless devices are in
range, have matching profiles assigned,
have fresh batteries, and are not in the
tampered condition. Initiate "Mesh
Formation mode" to actively search for
devices.
The offending device (detector or module
set at address 0 or module at the same
address as the gateway) will be indicating
the LED pattern for address fault. Find and
resolve that device.
Investigate for overlapping or adjacent
wireless systems produced by JCI.
Reduce the instances of overlap by
removing systems, or devices in the
overlapping region. Refer to Section 2.9.7
on the installation limits for the JCI
wireless system.
Operations

Advertisement

Table of Contents
loading

Table of Contents