Configuration and Programming
in their final mounting locations prior to initiating the mesh formation. The mesh formation is
initiated by the gateway upon user activation and terminated by the gateway when all possible
devices join the network or when terminated by the user.
To form a mesh network, ensure that the gateway is powered on and contains a profile. (Refer to
Section 2.5 on page 12 for information on how the gateway indicates its status). Activate the "Mesh
Formation" magnet sensor on the gateway. Refer to Figure 2.2 for sensor location.
The gateway will then transition to the mesh formation mode and establish communication with all
the devices containing a common profile. The blink pattern on the gateway indicates that it is in
mesh formation mode. At this stage, both the LEDs on the gateway will blink twice every 7 sec-
onds.
The first blink is green and the second blink is red when the gateway is acting as a profile
distributor and forming the mesh.
The first blink is green and the second blink is yellow when the gateway is only forming the
mesh.
Mesh formation typically takes one minute for each device in the mesh. Mesh formation automati-
cally terminates 10 minutes after the last device joins the mesh. Mesh formation can be terminated
manually by the user by again activating the mesh formation magnetic sensor.
Once the mesh formation is complete, the network automatically transitions to restructure the
mesh. For operating instructions, refer to Section 2.9, "Operations".
2.8.2 Configuration and Programming Using SWIFT Tools

Assign a Profile

To assign a profile to the gateway using SWIFT Tools:
1.
Connect the W-USB dongle device to your laptop. For more information on the USB dongle,
refer to Section 4, "USB Adapter", on page 43.
2.
Launch SWIFT Tools. Refer to Appendix A for more information.
3.
From the Home Screen, select the Create Mesh Network function.
4.
Create a new profile or Import an existing profile as required.
5.
Select and open the profile to be assigned to the gateway from the Name drop-down box in the
Profile section.
6.
Power on the gateway within approximately 20 feet of the laptop running SWIFT Tools.
7.
Ensure that the Scan On selection box in the Communicator Window is checked.
SWIFT™ Smart Wireless Integrated Fire Technology Manual — P/N LS10036-000JC-E:C 5/8/2015
Figure 2.8 Creating or Importing a Profile