contain the drive control parameters needed in the examples. For
a complete parameter list, see the drive documentation.
Starting up fieldbus communication for ACS355
drives
1. Power up the drive.
2. Enable the communication between the adapter module and
the drive with parameter 9802 COMM PROT SEL.
3. Set the FECA-01 configuration parameters in parameter group
51. At the minimum, select the communication profile with
parameter 5102.
4. Validate the settings made in parameter group 51 by setting
parameter 5127 FBA PAR REFRESH to REFRESH.
5. Set the relevant drive control parameters to control the drive
according to the application. If the CiA 402 profile is used, set
and check all parameters as instructed in the table below.
6. CiA 402 profile only: If you intend to use the CiA 402 profile,
do the following:
Select the desired operation mode for the adapter module
and the drive in CoE object 0x6060 by modifying the object
value via the master station. See section
modes of operation
Object
Dictionary.
Take into use suitable PDOs for the operation mode in use.
You can do this either via the default RxPDOs and
TxPDOs as described in section
page 93, or you can create your own custom PDOs as
well.
on page
68
and
Process Data Objects
Start-up 41
Supported
Appendix A – CoE
on