Feca-01 Configuration Parameters - Group A (Group 1) - ABB FECA-01 User Manual

Ethercat adapter module
Table of Contents

Advertisement

FECA-01 configuration parameters – group A (group 1)
Note: The actual parameter group number depends on the drive
type. Group A (group 1) corresponds to:
parameter group 51 in ACS355, ACSM1, ACS580 and
ACS850.
parameter group is typically 51/54 (group 151/154 in some
variants) in ACS880 if the adapter is installed as fieldbus
adapter A/B.
For more information, refer the appropriate drive manuals.
No.
Name/Value
01
FBA TYPE
02
PROFILE
ACS355:
FB PAR 2
ACSM1:
FBA PAR2
ACS850:
FBA par2
ACS880/ACS580:
Profile
0 = CiA 402
1 = ABB Drives
profile
3 = Transparent
Description
Read-only. Shows the fieldbus adapter type.
The value cannot be adjusted by the user.
If the value is not 135, the adapter module
sets the fieldbus configuration parameters to
their default values.
Selects the communication profile used by the
adapter module. It is not recommended to
switch communication profiles during
operation.
For more information on the communication
profiles, see chapter
CANopen device profile CiA 402 selected
ABB Drives profile selected
Transparent profile selected
Communication
profiles.
Start-up 35
Default
135 =
EtherCAT
0 =
CiA 402

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents