Redundancy Compatibility Parameter - Rdncmpt - Honeywell C300 User Manual

Series 8
Hide thumbs Also See for C300:
Table of Contents

Advertisement

8. C300 Redundancy operation
8.2. Redundancy configuration restrictions
1.
Factory data, such as: Vendor ID, Product Type, and Product Code must be identical
to ensure same platform hardware.
2.
Firmware Type must be identical ensure same platform firmware. Synchronization
cannot be allowed across different personalities.
3.
The Build ID strings are compared to detect difference in firmware versions. Some
platforms that use physical memory transfer as part of their redundancy solution are
sensitive to a difference in firmware versions. This includes C300.
4.
The partner module must have a properly configured Device Index. If this module
has an odd Device Index N, the partner module has to have the even Device Index
N+1. Otherwise, if this module has an even Device Index M, the partner module has
to have the odd Device Index M-1.

Redundancy compatibility parameter - RDNCMPT

The RDNCMPT parameter indicates the following compatibility results.
RDNCMPT
Parameter
- - -
NOPARTNER
QUERYINPROG
COMPATIBLE
DIRECTCMPT
MESSAGESIZE
VENDORID
PRODUCTTYPE
PRODUCTCODE
MAJREVISION
MINREVISION
210
State
Not Applicable
Module is configured as non-redundant.
Not Applicable
Initial/default state when no partner is responding to the
partner compatibility query.
Not Applicable
Transient state while partner compatibility check is
being performed.
Compatible
Compatible indication for those platforms not sensitive
to difference in firmware versions.
This includes FIM, Series 8 FIM, and IOLINK.
Compatible
Compatible indication for those platforms sensitive to
difference in firmware versions (that is, C300) when
firmware versions are identical.
Incompatible
The size of the partner's compatibility message is
unexpected.
Incompatible
The partner's Vendor ID does not match.
Incompatible
The partner's Product Type does not match.
Incompatible
The partner's Product Code does not match.
Incompatible
The partner's Major revision is not supported.
Incompatible
The partner's Minor revision is not supported.
Series 8 C300 Controller User's Guide
Honeywell
Description
R500
April 2017

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents